GeniSys® Lockout Alarm Module | 52040

The Beckett GeniSys® Lockout Alarm 52040 functions as the interface between the GeniSys® 7505 120V Oil Burner Control and an existing alarm panel. The 52040U will provide a contact closure in the event of a soft or hard burner lockout.

NOTE: Not compatible with any other series burner control.

Details

Specifications

  • Maximum Alarm Module Contact Switching Current:
    2 Amps (ac or dc)
  • Minimum Alarm Module Contact Switching Current:
    5 mA (ac or dc)
  • Maximum Alarm Module Switching Voltage:
    30V (ac or dc)
  • Minimum Alarm Module Switching Voltage:
    5V (ac or dc)
  • Storage & Operating Ambient Temperature:
    -40°F to +1500°F (-40°C to +65°C)
  • Humidity (noncondensing & non-crystalizing):
    5 to 95% RH

Operation

When power is applied to the primary control, the alarm module continuously monitors the GeniSys control for both a hard and soft lockout signal. If the alarm module detects either a hard or soft lockout, normally open relay contacts on the module close, creating a short circuit between the output terminals. When the alarm module no longer senses a lockout signal or power is removed from the control, the module relay contacts will open.

Installation

Install the alarm module by carefully sliding the module onto the COM 1 port located on the right side of the control. Referring to the diagram on the back page, connect the wires from an existing alarm panel in series with the two terminals on top of the module.

Typical Alarm Light or Buzzer Connection

Typical Security Panel Connection

Downloads & Links

Warranty

Please note, all warranty claims must be initiated through an authorized Beckett supplier/distributor. Distribution policies will not allow Beckett to directly handle warranty claims with installers and/or consumers.

Click to view Limited Warranty for Beckett Products.

Click here to check if your part is still under warranty

Beckett Training is Now Online

Informative and technical training resources from the leading experts in the heating industry

We're Here to Help!

Have questions about our products? Looking for a solution to address a particular application? Looking to improve the overall productivity and profitability of your operation? Please don’t hesitate to reach out or schedule a no obligation, 1-on-1 consultation with a Beckett Technical Specialist — we’d love to help.

Where to Buy

Beckett solutions are available through our network of Distributors, Independent Representatives, and Export Representatives all around the world.