This bulletin advises that Cleancut pumps A2EA-6527 manufactured during months March, April and May 2016 might present a tightness issue on Inlet/Return ¼-18 NPTF plugs.

 

 

In order to identify such pumps, it is necessary to check the date stamped on the top of the body:

cleancut-pump

 

 

  1. Before starting your burner, confirm the pump is not in the affected date range.
    If the unit is in the date range, follow steps 2 and 3.
  2. Carefully verify the tightness of Inlet/Return plugs.
  3. For any recognized or suspected leak, unscrew plugs and apply pipe sealant, and re-insert them with a fitting torque of 12 to 20 Ft.Lbs.

You can also download a printer-friendly version of this bulletin.

Beckett Training is Now Online

Informative and technical training resources from the leading experts in the heating industry

We're Here to Help!

Have questions about our products? Looking for a solution to address a particular application? Looking to improve the overall productivity and profitability of your operation? Please don’t hesitate to reach out or schedule a no obligation, 1-on-1 consultation with a Beckett Technical Specialist — we’d love to help.